
Programming Manual EURO
RINS1291-3 Page: 27
4.9 Change Timers
All the timers can be changed in this function, the table below shows the different timers
available and the default values:
Timer Function Range Default
Entry Time Entry time for each area. 0 – 255 secs
30
Exit Time Exit time for each area. 0 – 255 secs
30
Siren Time Cut off time for external sounder. Separate for each area. 2 – 15 minutes
15
Confirm
Time
Time period during which a second activation must occur
to qualify as ‘sequentially confirmed’ alarm. NOTE:
DD243 specifies a confirm time between 30 and 60
minutes. This also can be used in conjunction with
testing an omit signal.
1 – 99 minutes 30
Siren Delay Delay after intruder alarm before siren live. NOT valid
within 3 minutes of final set or after entry time
started.
0 – 20 minutes 0
Strobe Time Time strobe output remains live after siren time ends.
‘99’ means endless.
0 – 99 minutes 0
Re-Arm No. Number of times system re-arms after bell time ends.
NOTE: Re-arm number applies to each area, and
does not affect emergency alarms. ‘9’ means always
re-arm.
0 – 9 3
AC Signal
Delay
Time delay before mains failure or technical alarm
notified. NOTE: Setting ‘250’ = never alarms. System
change-over to battery supply and associated visual
alert indication is always immediate.
Some ATE impose a randomised delay in notifying a
mains fail. This should be taken into account when setting
this timer.
0 – 250
minutes
40
Speaker Time speaker and keypad bleeper outputs remain
live after siren time ends. ‘99’ means endless.
0 – 250
minutes
0
Settle Time between final exit input closing, and system setting. 0 - 255 seconds 5
Double
Knock
Length of filter period applied to inputs with ‘Double
Knock’ attribute.
0 – 75 seconds 10
Pre-Alarm Delays ‘Intruder’ output signals if entry time has started.
Pre-alarm time must be set for at least 30 seconds
to comply with PD6662
0 – 255
seconds
30
Line Fault Duration of Telecom Line Fault before ‘Line Fault’ alarm
triggered. NOTE: In the case of devices connected via the
ATE pins, this time is additional to that already applied by
the ATE.
0 – 250
seconds
20
Set Fail Time after which ‘Set Fail’ operation will be invoked if exit
procedure not completed.
0 – 255
seconds
40
Guard Code
Alarm*
Minimum time an alarm must have existed before a
‘Guard’ code will be accepted to unset.
0 – 10 minutes 3
Fire Bell
Time
Cut off time for fire alarm.
‘99’ means endless.
1 – 99 minutes 99
Input NAT
Days*
NAT stands for Non-Activity. This is used in conjunction
with the input attribute ‘Monitor Activity’, and will monitor
the chosen input for the selected number of days.
0-14 14
Input NAT
Hours*
NAT stands for Non-Activity. This is used in conjunction
with the input attribute ‘Monitor Activity’, and will monitor
the chosen input for the selected number of hours.
00-23 0
Service
Time*
This is a timer that can be set in days, and will display a
message to the user warning that a service is due. An
engineer code will clear the message.
367 0
NOTE: Control of timer for inputs on Set fail test is located in the Engineer Tests Sub
Menu. *These are not available on the Euro 28.
Kommentare zu diesen Handbüchern