Started Manual Castle Care-Tech Ltd
5·00 Page 35
Timer
Function
Range
Default
AC
signal
Delay
Time delay
before Mains
failure or
Technical alarm
generated
0
250
mins
60
Note: setting ‘250’ = never alarms.
System change-over to battery
supply, and associated visual ‘Mains
Fail’ indication is always immediate.
Spea
-
ker
Time
Time Speaker
and Keypad
Bleeper outputs
stay live after
end of Siren
time
0
99
mins
0
99’ represents endless
Settle
Time after exit
procedure is
complete
before system
is active (to
permit exit
route detectors
to settle).
0
255
secs
05
Double
Knock
Length of filter
period applied
to
double
knock
zones
0
75
secs
10
Pre
-
Alarm
Delays
intruder
output signal if
entry time has
started
0
255
secs
030
30 secs is minimum required for
PD6662 systems
Line
Fault
Duration of ATS
Path Fault
before triggers
Line Fault
alarm
0
250
secs
20
Timer
Function
Range
Default
Set
Fail
Time after
which
Set Fail
operation will
be invoked if
exit procedure
not completed.
Starts
coincident with
exit sequence.
5
255
secs
00
0
10
mins
03
Guard
Code
Alarm
Minimum time
an alarm must
have existed
before system
permits a
Guard code
to
unset.
Fire
Siren
Cut off time for
Fire alarm
0
99
mins
99
99’ represents endless
Soak Test timer is located in
'Engineer Tests' - see page 45.
PROGRAMMING PROCEDURE:
With the display showing
CHANGE TIMERS?
Press YES
A Entry Time
[030]
Adjust time as required, with
numeric keys and press YES
A Exit Time
[030]
Repeat for each timer . . .
Press NO
CHANGE TIMERS?
Press NO
Moves to next menu item
N
ote: Timer
s
ettin
g
250 is
E
ndless
Castle Care-Tech Ltd Euro-MERiDIAN Getting
Page 36 Software
EXIT MODES
The exit mode can be set
individually for each Security
pattern or Area. The modes
available are
Timed mode: sets the system
when the programmed exit time
has expired, provided all
detectors on the exit route are
clear. Any PTS button fitted will
be live also in this mode.
Final Door mode: the setting
procedure will be completed
when an input programmed as
Final Exit (FX) is closed. This
mode may also be used for lock
set operation: securing the lock
completes setting procedure,
unlocking starts entry time.
Timed/Final mode: sets in the
same way as Timed mode,
except that the timer will be
overridden if a final exit (FX)
input is opened and closed
before it expires.
PTS mode: will ignore the
programmed exit time for the
area in question, and will be
endless.
Note: The PTS signal is NOT stored.
If pressed before the exit route is
clear, it will be ignored.
SILENT SETTING
There is no 'silent set' option as
such. However, this function can
be achieved by careful use of the
'volume control' options,
especially volume level 1 (see
page 39).
Intelligent Setting
See page 43 for details.
DD243:2004
The Euro-MERiDIAN range is fully
compliant with the requirements
of DD243:2004, having a full
range of setting and unsetting
modes available for any
requirement.
See full Engineering Manual for
additional information.
PROGRAMMING STEPS:
With the display showing
EXIT MODES?
Press YES
A Exit mode
Timed [0]
Use
D
to select between
Timed [0]
Final Door [1]
PTS [2]
and
Door/Timed [3]
for level/area A.
Press YES
B Exit mode
Timed [0]
Repeat for area B, etc.
Press YES
EXIT MODES?
Press NO
Moves to next menu item