Started Manual Castle Care-Tech Ltd
4·00 Page
25
11. PROGRAMMING THE SYSTEM
CLEAN START
It is essential that a ‘clean start’
be performed at initial power up
of a new system, to ensure that
the initialisation is correct to
true factory defaults.
If the Non-Volatile Memory (NVM)
chip is ever removed from the
End Station, it MUST be replaced
before starting programming.
To perform a ‘clean start’:
With the display showing
CLEAN START?
Press YES
Clean Start?
[ ]
Enter
2000
Clean Start?
Please Wait
Panel has been
clean started!
Press YES
Clear Codes?
If you wish to keep the
existing codes on the
system press NO,
otherwise press ‘Yes’
Initialise Logs?
Press ‘Yes’ to clear logs
The system memory will now be
restored to factory defaults,
EXCEPT:
Keypad 00 remains enabled
at all times
Keypad in use remains
enabled.
Current Keypad areas are
NOT changed
Note: If a new NVM chip is to be
used, Logs must be cleared (see
page 49)
INHIBIT FIRE/HU?
It is possible to prevent the panel
from alarming from fire or Hold
Up zones whilst in engineering
menu through this option. Please
be aware of the potential liability
and hazard of inhibiting these
zone types.
INHIBIT FIRE/HU?
When you come out of
engineering, the inhibited zones
will be re-instated automatically.
SOFTWARE REVISION
Selecting this option will display
the software version fitted to
the system, eg
Rev 5.00 UK
12345678 G3+74
This identifies the software
version number, software serial
Castle Care-Tech Ltd Euro-MERiDIAN Getting
Page 26 Software
number and product, and should
always be checked before
contacting Technical Support.
MODE SELECTION
The G3+ panel defaults to accept
‘End of Line’ wiring, but may be
programmed to use ‘iD’
technology by changing the
setting in the ‘Mode’ menu. The
G2-EoL endstation is EoL only and
G2-iD is iD only.
With display showing
CHANGE MODE?
Press YES
Detection Mode
EoL [ 1]
Use
D
to select between
iD [0] and EOL [1]
(
on Euro G3+ & above only)
Press YES
EOL Mode
DR [ 1]
Do
not
adjust this setting
unless single-resistor
wiring is to be used.
Press YES
Zone Response
400 mS [08]
Do
not
adjust this setting
Press YES
Zone XDF
Off [0]
DO NOT CHANGE THIS
SETTING, unless specifically
advised to do so by Castle
Care-Tech Ltd Technical
Support staff.
Press YES
CHOOSE MODE?
Press NO
Moves to next menu item
NOTES:
On systems with Zone Expander
Modules fitted, the zones will be
arranged as shown in the table on
page 27,28.
Zones wired from Keypads / Tag
Readers will ALWAYS be ‘End of
Line,’ regardless of mode selected.
ENABLE ZEMS
Before a ZEM can be used, it
must be correctly addressed (see
page 9) AND enabled in software
as follows:
With display showing
ENABLE ZEMs?
Press YES
ZEM Address
[ 0]
Select ZEM to be enabled,
eg press
1
and YES
ZEM Installed
No [0]
Use
D
to select
‘
Yes [1]
’
and press YES
ZEM Address
[ 1]
Repeat for additional
ZEMs or Press NO