5·00 Page 31
ZONE ATTRIBUTES
Attribute Response modification
Chime
System loudspeaker(s) will
‘chime’ when detector triggered
whilst relevant area is unset.
Note: zone concerned will NOT
indicate on display.
Single
System chimes once when
detector triggered
Follow
System chimes until detector is
cleared.
Applicable to ‘Intruder’ ‘FX’ ‘EN’ and
‘Switcher’ zones.
Omittable
Enables input to be manually
omitted during the setting
procedure
Normally
Open
Enables the system to respond
correctly when detectors of
‘normally open’ configuration
are wired to the system.
Alternatively converts input
types which default to ‘normally
open’ (eg PTS) to operate with
normally closed devices.
Double
knock
The control will only generate an
alarm if this input is triggered
twice within a pre-set period, or
if the input remains open for
that period.
Dual Trip
The Control will only generate an
alarm if this input, and another
like-programmed input
with
adjacent number
, are in active
condition at the same time.
Either detector in fault
condition will prevent the
system from setting.
Both
detectors must be wired
using the same technology (iD
or EoL) from the same device.
Special
Logged
Forces a log entry when the
input is opened or closed, even
when an alarm does not result.
May be selected to apply when
system is set, when unset, or
always.
Attribute Response modification
This attribute MUST be selected
for switcher inputs required to
activate SMS text messages.
Paired
Input
For use in Grade 3 iD systems.
Select to ‘YES’ for each of the
two biscuits acting as the input.
(see page 12 & 13)
Fault
Input
For use in Grade 3 iD systems.
Select to ‘YES’ for the biscuit
acting as the ‘anti-mask’ (biscuit
2 in figure 3 page 12)
Paired
With
For both biscuits enter the input
number with which each is
paired (see page 13).
Confirm
Group
Input will not 'confirm' an alarm
triggered by another input from
the same group. Groups 01 to 99
available.
Default '00' denotes
NOT part of a group.
Inputs allocated to ‘Group 99’
will generate an alarm that
results in an intruder
(unconfirmed) signal to ARC.
They will NOT under ANY
circumstances generate a
confirmed signal, regardless of
which group the input that
triggered the ‘unconfirmed’
alarm is allocated to.
See full Engineering Manual for
further details.
Any input may be programmed with
any combination of these attributes,
except where shown.
NOTE: Control of inputs on SOAK TEST
is located in the 'Engineer
Tests' menu -
page 46.
Castle Care-Tech Ltd Euro-MERiDIAN Getting
Software Page 32
PROGRAMMING STEPS
With the display showing
CHANGE INPUTS?
Press YES
Input Number
[01]
Press YES
Input Type
Isolated [00]
EITHER use
D
to scroll to
required setting OR key in
input type number from
table above – eg 07
n
u
e
Final Exit [07]
Press YES
Input Areas
[ABCD]
Use keys
to select the
security patterns required,
eg press
AB
Input Areas
[AB ]
Whilst programming this
step, the keypad Area
(A,B,C,D) keys will illuminate
when that pattern is
selected.
Press YES
Input
Attributes?
Press YES
Chime
No [0]
Use
D
to select No [0],
Single [1] or Follow [2]
Press YES
Omittable
No [0]
Continue to select input
attribute options as
required, until
Input Name?
Press YES
n
er
n
u
ame
I
nput 01
Enter text to identify
input, as described on
page 23.
Press YES
Input Number
EITHER key in next input
number to programme, or
NO to exit function
CHANGE INPUTS?
Press NO
Moves to next menu
item
NOTE:
After programming the input, it is
necessary to exit engineering for
this to take effect, before the input
can be walk tested, etc.